ZIGBEE ETHERNET GATEWAY DATA CONTRACT AND BENCH TEST Companion: https://yenra.com/zigbee-ethernet-gateway/ Prepared September 8, 2026. Read-only integration planning on approved equipment. INSTRUCTIONS Fill every address and field from the exact manufacturer's documentation. A radio or Ethernet connection alone does not establish application compatibility. Do not use the fictional example below as a real device register map. Gateway / firmware / manual revision / operating mode: Sensor or serial endpoint / firmware / supported function evidence: Ethernet API/protocol and security / allowed clients / management path: Wireless role / device identity / gateway-side identity mapping: COPY PER VALUE Measured quantity / unit: API field or Modbus function code / unit ID / zero-based protocol address: Register count / manual's displayed address convention: Data type / signedness / byte order / multi-register word order: Scale / offset / invalid-value convention: Measurement time / receipt time / reporting interval: Quality flag / maximum data age / stale-data behavior: Known input / raw read / calculated value / observed application value: FICTIONAL EXAMPLE ONLY Function 04, input-register protocol address 0, signed 16-bit, scale 0.1 C/count. 234 -> 23.4 degrees C; -55 -> -5.5 degrees C. A separate hypothetical quality/time contract marks old data stale even if the cached value remains readable. These fields are not an ICP DAS register map. BENCH TEST LOG Timestamp/timezone / test / expected outcome / actual outcome / evidence: Known normal, negative or boundary input: Incorrect address or documented protocol exception: Sensor-report interruption and stale indication: Ethernet interruption and timeout behavior: Reconnection / buffered records / original timestamps / duplicates: Polling interval / retries / outstanding requests and capacity evidence: Correction / retest / acceptance decision: RETAIN Completed map, exact models/versions, manual, approved configuration and owner. Recheck after sensor, gateway, firmware or application changes. Consult the Modbus specification and exact gateway manual linked from the companion guide.